Overview
The voltage/current signal sensor is specially designed for power supply monitoring for fire equipment in accordance with
national standard GB28184-2011 "Power supply monitoring system for fire protection equipment". When the power supply for fire
protection equipment fails (interruption, overvoltage, undervoltage, phase loss, overload, etc.), the sensor will upload the fault
alarm data and measurement data to the fire protection equipment power monitor through the communication interface.
national standard GB28184-2011 "Power supply monitoring system for fire protection equipment". When the power supply for fire
protection equipment fails (interruption, overvoltage, undervoltage, phase loss, overload, etc.), the sensor will upload the fault
alarm data and measurement data to the fire protection equipment power monitor through the communication interface.
Technical parameter table
Models and specifications | TY-DY-3V3A | TY-DY-3V6A | TY-DY-6V3A | TY-DY-9V | TY-DY-D6V |
One way of three-phase current / One way of three-phase voltage | Two ways of three-phase current / one way of three-phase voltage | One way of three-phase current / two ways of three-phase voltage | Three ways of three-phase voltage | Six ways of single-phase voltage | |
Monitoring objects | <0.4W | ||||
Rated power | Non-polarity two-bus | ||||
Communication mode | NH-RVS-2×2.5 mm² | ||||
Cable specification | Each sensor has a unique address code | ||||
Address code | Undervoltage < 85% of rated voltage, overvoltage > 110% of rated voltage,overcurrent O-1000 A, user defined | ||||
Ambient temperature | -15℃~55℃ | ||||
Ambient humidity | Relative humidity ≤ 95% | ||||
Altitude | <2000m | ||||
IP rating | IP30 | ||||
Outline dimensions | 70×63×85mm (W × D × H) | ||||
Installation method | Standard 35 mm rail-mounted/surface-mounted with screws |