Overview

The voltage/current signal sensor is specially designed for power supply monitoring for fire equipment in accordance with
national standard GB28184-2011 "Power supply monitoring system for fire protection equipment". When the power supply for fire
protection equipment fails (interruption, overvoltage, undervoltage, phase loss, overload, etc.), the sensor will upload the fault
alarm data and measurement data to the fire protection equipment power monitor through the communication interface.

Technical parameter table

Models and specifications TY-DY-3V3A TY-DY-3V6A TY-DY-6V3A TY-DY-9V TY-DY-D6V
  One way of three-phase current / One way of three-phase voltage Two ways of three-phase current / one way of three-phase voltage One way of three-phase current / two ways of three-phase voltage Three ways of three-phase voltage Six ways of single-phase voltage
Monitoring objects <0.4W
Rated power Non-polarity two-bus
Communication mode NH-RVS-2×2.5 mm²
Cable specification Each sensor has a unique address code
Address code Undervoltage < 85% of rated voltage, overvoltage > 110% of rated voltage,overcurrent O-1000 A, user defined
Ambient temperature  -15℃~55℃
Ambient humidity Relative humidity ≤ 95%
Altitude <2000m
IP rating IP30
Outline dimensions 70×63×85mm (W × D × H)
Installation method Standard 35 mm rail-mounted/surface-mounted with screws